Enhanced Grid Following Inverter (E-GFL): A Unified Control Framework for Stiff and Weak Grids

Fuente: arXiv
Saved in:
Bibliographic Details
Main Authors: Askarian, Alireza, Park, Jaesang, Salapaka, Srinivasa
Format: Preprint
Published: 2023
Subjects:
Online Access:
Tags: Add Tag
No Tags, Be the first to tag this record!
_version_ 1866910307123724288
author Askarian, Alireza
Park, Jaesang
Salapaka, Srinivasa
author_facet Askarian, Alireza
Park, Jaesang
Salapaka, Srinivasa
contents This paper presents an extensive framework focused on the control design, along with stability and performance analysis, of Grid-Following Inverters (GFL). It aims to ensure their effective operation under both stiff and weak grid conditions. The proposed framework leverages the coupled algebraic structure of the transmission line dynamics in the $dq$ frame to express and then mitigate the effect of coupled dynamics on the GFL inverter's stability and performance. Additionally, we simplify the coupled multi-input, multi-output (MIMO) closed-loop system of the GFL into two separate single-input, single-output (2-SISO) closed-loops for easier analysis and control design. We present the stability, robust stability, and performance of the original GFL MIMO closed-loop system through our proposed 2-SISO closed-loop framework. This approach simplifies both the control design and its analysis. Our framework effectively achieves grid synchronization and active damping of filter resonance via feedback control. This eliminates the need for separate phase-locked loop (PLL) and virtual impedance subsystems. We also utilize the Bode sensitivity integral to define the limits of GFL closed-loop stability margin and performance. These fundamental limits reveal the necessary trade-offs between various performance goals, including reference tracking, closed-loop bandwidth, robust synchronization, and the ability to withstand grid disturbances. Finally, we demonstrate the merits of our proposed framework through detailed simulations and experiments. These showcase its effectiveness in handling challenging scenarios, such as asymmetric grid faults, low voltage operation, and the balance between harmonic rejection and resonance suppression.
format Preprint
id arxiv_https___arxiv_org_abs_2304_02792
institution arXiv
publishDate 2023
record_format arxiv
spellingShingle Enhanced Grid Following Inverter (E-GFL): A Unified Control Framework for Stiff and Weak Grids
Askarian, Alireza
Park, Jaesang
Salapaka, Srinivasa
Systems and Control
This paper presents an extensive framework focused on the control design, along with stability and performance analysis, of Grid-Following Inverters (GFL). It aims to ensure their effective operation under both stiff and weak grid conditions. The proposed framework leverages the coupled algebraic structure of the transmission line dynamics in the $dq$ frame to express and then mitigate the effect of coupled dynamics on the GFL inverter's stability and performance. Additionally, we simplify the coupled multi-input, multi-output (MIMO) closed-loop system of the GFL into two separate single-input, single-output (2-SISO) closed-loops for easier analysis and control design. We present the stability, robust stability, and performance of the original GFL MIMO closed-loop system through our proposed 2-SISO closed-loop framework. This approach simplifies both the control design and its analysis. Our framework effectively achieves grid synchronization and active damping of filter resonance via feedback control. This eliminates the need for separate phase-locked loop (PLL) and virtual impedance subsystems. We also utilize the Bode sensitivity integral to define the limits of GFL closed-loop stability margin and performance. These fundamental limits reveal the necessary trade-offs between various performance goals, including reference tracking, closed-loop bandwidth, robust synchronization, and the ability to withstand grid disturbances. Finally, we demonstrate the merits of our proposed framework through detailed simulations and experiments. These showcase its effectiveness in handling challenging scenarios, such as asymmetric grid faults, low voltage operation, and the balance between harmonic rejection and resonance suppression.
title Enhanced Grid Following Inverter (E-GFL): A Unified Control Framework for Stiff and Weak Grids
topic Systems and Control
url https://arxiv.org/abs/2304.02792