Analytical Formula for Calculations of Armour Losses in Three-Core Power Cables

Fuente: arXiv
Salvato in:
Dettagli Bibliografici
Autori principali: Hatlo, Marius, Hovde, Martin
Natura: Preprint
Pubblicazione: 2024
Soggetti:
Accesso online:
Tags: Aggiungi Tag
Nessun Tag, puoi essere il primo ad aggiungerne!!
_version_ 1866911834581237760
author Hatlo, Marius
Hovde, Martin
author_facet Hatlo, Marius
Hovde, Martin
contents Over the past decade, significant progress has been made in the field of loss and rating calculations for armoured three-core cables. This development was prompted by an industry realization that the applicable international standards often overestimate losses, leading to unnecessarily bulky and more expensive cables. Starting with first-principles, this paper presents an accurate analytical formula for armour losses in three-core cables. The formula has undergone rigorous validation against 3D Finite Element Analysis (FEA) and demonstrate excellent accuracy. In the specific cases examined, the largest deviation from FEA results in terms of armour loss is approximately 2.4 percent for fully armoured cables. Although this study specifically focuses on armour losses, it establishes the groundwork for precise loss calculations in armoured three-core cables, including the conductor and screen losses. And the work presented here formed the basis for the complete loss calculations presented in the CIGRE Technical Brochure 908.
format Preprint
id arxiv_https___arxiv_org_abs_2404_06998
institution arXiv
publishDate 2024
record_format arxiv
spellingShingle Analytical Formula for Calculations of Armour Losses in Three-Core Power Cables
Hatlo, Marius
Hovde, Martin
Systems and Control
Over the past decade, significant progress has been made in the field of loss and rating calculations for armoured three-core cables. This development was prompted by an industry realization that the applicable international standards often overestimate losses, leading to unnecessarily bulky and more expensive cables. Starting with first-principles, this paper presents an accurate analytical formula for armour losses in three-core cables. The formula has undergone rigorous validation against 3D Finite Element Analysis (FEA) and demonstrate excellent accuracy. In the specific cases examined, the largest deviation from FEA results in terms of armour loss is approximately 2.4 percent for fully armoured cables. Although this study specifically focuses on armour losses, it establishes the groundwork for precise loss calculations in armoured three-core cables, including the conductor and screen losses. And the work presented here formed the basis for the complete loss calculations presented in the CIGRE Technical Brochure 908.
title Analytical Formula for Calculations of Armour Losses in Three-Core Power Cables