On the input admittance of a universal power synchronization controller with droop controllers

Fuente: arXiv
Saved in:
Bibliographic Details
Main Authors: Karaca, Orcun, Subotic, Irina, Harnefors, Lennart, Tsoumas, Ioannis
Format: Preprint
Published: 2025
Subjects:
Online Access:
Tags: Add Tag
No Tags, Be the first to tag this record!
_version_ 1866912442943012864
author Karaca, Orcun
Subotic, Irina
Harnefors, Lennart
Tsoumas, Ioannis
author_facet Karaca, Orcun
Subotic, Irina
Harnefors, Lennart
Tsoumas, Ioannis
contents Recent work has proposed a universal framework that integrates the well-established power synchronization control into vector current control. Using this controller for the parallel operation of grid-forming converters, and/or with loads that have strong voltage magnitude sensitivity, requires additional loops manipulating the voltage magnitude, e.g., $QV$ and $PV$ voltage-power droop controllers. This paper derives the input admittance of the resulting overall scheme. Sensitivity analyses based on the passivity index demonstrate the benefits of the proportional components of $QV$ and $PV$ control. A case study is presented where a grid-forming converter is operated in parallel with a generator.
format Preprint
id arxiv_https___arxiv_org_abs_2506_17044
institution arXiv
publishDate 2025
record_format arxiv
spellingShingle On the input admittance of a universal power synchronization controller with droop controllers
Karaca, Orcun
Subotic, Irina
Harnefors, Lennart
Tsoumas, Ioannis
Systems and Control
Recent work has proposed a universal framework that integrates the well-established power synchronization control into vector current control. Using this controller for the parallel operation of grid-forming converters, and/or with loads that have strong voltage magnitude sensitivity, requires additional loops manipulating the voltage magnitude, e.g., $QV$ and $PV$ voltage-power droop controllers. This paper derives the input admittance of the resulting overall scheme. Sensitivity analyses based on the passivity index demonstrate the benefits of the proportional components of $QV$ and $PV$ control. A case study is presented where a grid-forming converter is operated in parallel with a generator.
title On the input admittance of a universal power synchronization controller with droop controllers
topic Systems and Control
url https://arxiv.org/abs/2506.17044