Robust black start of an offshore wind farm with DRU based HVDC link using power synchronization control

Fuente: arXiv
Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Karaca, Orcun, Tsoumas, Ioannis, Schweizer, Mario, Stanojev, Ognjen, Harnefors, Lennart
Format: Preprint
Veröffentlicht: 2025
Schlagworte:
Online-Zugang:
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
_version_ 1866908414960992256
author Karaca, Orcun
Tsoumas, Ioannis
Schweizer, Mario
Stanojev, Ognjen
Harnefors, Lennart
author_facet Karaca, Orcun
Tsoumas, Ioannis
Schweizer, Mario
Stanojev, Ognjen
Harnefors, Lennart
contents This paper introduces a universal power synchronization controller for grid-side control of the wind turbine conversion systems in an offshore wind farm with a diode rectifier in the offshore substation of the HVDC link. The controller incorporates voltage-power droop controllers in the outer loop to enable the operation of this setup. To effectively handle the impact of large delays during black start and power ramp phases, virtual active and reactive power quantities are defined. These quantities are computed based on the current references prior to any modifications that might be needed to meet converter current and voltage limits or source constraints. Utilizing them in the outer loop ensures a balanced power sharing and a stable operation whenever the original (unmodified) current references are not realized. Case studies confirm the robustness of the proposed controller.
format Preprint
id arxiv_https___arxiv_org_abs_2506_17060
institution arXiv
publishDate 2025
record_format arxiv
spellingShingle Robust black start of an offshore wind farm with DRU based HVDC link using power synchronization control
Karaca, Orcun
Tsoumas, Ioannis
Schweizer, Mario
Stanojev, Ognjen
Harnefors, Lennart
Systems and Control
This paper introduces a universal power synchronization controller for grid-side control of the wind turbine conversion systems in an offshore wind farm with a diode rectifier in the offshore substation of the HVDC link. The controller incorporates voltage-power droop controllers in the outer loop to enable the operation of this setup. To effectively handle the impact of large delays during black start and power ramp phases, virtual active and reactive power quantities are defined. These quantities are computed based on the current references prior to any modifications that might be needed to meet converter current and voltage limits or source constraints. Utilizing them in the outer loop ensures a balanced power sharing and a stable operation whenever the original (unmodified) current references are not realized. Case studies confirm the robustness of the proposed controller.
title Robust black start of an offshore wind farm with DRU based HVDC link using power synchronization control
topic Systems and Control
url https://arxiv.org/abs/2506.17060