String-Level Ground Fault Localization for TN-Earthed Three-Phase Photovoltaic Systems

Fuente: arXiv
Guardado en:
Detalles Bibliográficos
Autores principales: Li, Yuanliang, Gong, Xun, Iravani, Reza, Cao, Bo, Liu, Heng, Chen, Ziming
Formato: Preprint
Publicado: 2026
Materias:
Acceso en línea:
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
_version_ 1866917275335917568
author Li, Yuanliang
Gong, Xun
Iravani, Reza
Cao, Bo
Liu, Heng
Chen, Ziming
author_facet Li, Yuanliang
Gong, Xun
Iravani, Reza
Cao, Bo
Liu, Heng
Chen, Ziming
contents The DC-side ground fault (GF) poses significant risks to three-phase TN-earthed photovoltaic (PV) systems, as the resulting high fault current can directly damage both PV inverters and PV modules. Once a fault occurs, locating the faulty string through manual string-by-string inspection is highly time-consuming and inefficient. This work presents a comprehensive analysis of GF characteristics through fault-current analysis and a simulation-based case study covering multiple fault locations. Building on these insights, we propose an edge-AI-based GF localization approach tailored for three-phase TN-earthed PV systems. A PLECS-based simulation model that incorporates PV hysteresis effects is developed to generate diverse GF scenarios, from which correlation-based features are extracted throughout the inverter's four-stage shutdown sequence. Using the simulated dataset, a lightweight Variational Information Bottleneck (VIB)-based localization model is designed and trained, achieving over 93% localization accuracy at typical sampling rates with low computational cost, demonstrating strong potential for deployment on resource-constrained PV inverters.
format Preprint
id arxiv_https___arxiv_org_abs_2602_12289
institution arXiv
publishDate 2026
record_format arxiv
spellingShingle String-Level Ground Fault Localization for TN-Earthed Three-Phase Photovoltaic Systems
Li, Yuanliang
Gong, Xun
Iravani, Reza
Cao, Bo
Liu, Heng
Chen, Ziming
Systems and Control
Machine Learning
Signal Processing
The DC-side ground fault (GF) poses significant risks to three-phase TN-earthed photovoltaic (PV) systems, as the resulting high fault current can directly damage both PV inverters and PV modules. Once a fault occurs, locating the faulty string through manual string-by-string inspection is highly time-consuming and inefficient. This work presents a comprehensive analysis of GF characteristics through fault-current analysis and a simulation-based case study covering multiple fault locations. Building on these insights, we propose an edge-AI-based GF localization approach tailored for three-phase TN-earthed PV systems. A PLECS-based simulation model that incorporates PV hysteresis effects is developed to generate diverse GF scenarios, from which correlation-based features are extracted throughout the inverter's four-stage shutdown sequence. Using the simulated dataset, a lightweight Variational Information Bottleneck (VIB)-based localization model is designed and trained, achieving over 93% localization accuracy at typical sampling rates with low computational cost, demonstrating strong potential for deployment on resource-constrained PV inverters.
title String-Level Ground Fault Localization for TN-Earthed Three-Phase Photovoltaic Systems
topic Systems and Control
Machine Learning
Signal Processing
url https://arxiv.org/abs/2602.12289