A Data-Aided Power Transformer Differential Protection without Inrush Blocking Module

Fuente: arXiv
Guardado en:
Detalles Bibliográficos
Autores principales: Lin, Zexuan, Yang, Songhao, Zhang, Yubo, Hao, Zhiguo, Zhang, Baohui
Formato: Preprint
Publicado: 2026
Materias:
Acceso en línea:
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
_version_ 1866917380254334976
author Lin, Zexuan
Yang, Songhao
Zhang, Yubo
Hao, Zhiguo
Zhang, Baohui
author_facet Lin, Zexuan
Yang, Songhao
Zhang, Yubo
Hao, Zhiguo
Zhang, Baohui
contents When a slightly faulty transformer closes without load, the current waveform presents the coexistence of inrush and fault current. At this time, the inrush blocking module will block the relay, which may delay the removal of the slight fault and lead to more serious faults. To address this problem, this paper proposes a data-aided power transformer differential protection without inrush blocking module. The key to eliminating the negative influence of inrush current is to extract the fundamental component from the non-inrush part of the current waveform, which corresponds to the unsaturation period of the transformer core. Firstly, a data-aided module, namely an Attention module embedded Fully Convolutional Network (A-FCN), is built to distinguish the inrush and non-inrush parts of the current waveform. Then, a physical model of the current waveform is built for the non-inrush part, and the fundamental component is extracted by the nonlinear least square (NLS) algorithm. The proposed method can avoid the block of differential protections when inrush current occurs, which improves the sensitivity and rapidity of the relay, especially in the case of a weak internal fault hidden in inrush current. Finally, simulation and experimental data verify the effectiveness and generalization of the proposed method.
format Preprint
id arxiv_https___arxiv_org_abs_2604_01928
institution arXiv
publishDate 2026
record_format arxiv
spellingShingle A Data-Aided Power Transformer Differential Protection without Inrush Blocking Module
Lin, Zexuan
Yang, Songhao
Zhang, Yubo
Hao, Zhiguo
Zhang, Baohui
Systems and Control
When a slightly faulty transformer closes without load, the current waveform presents the coexistence of inrush and fault current. At this time, the inrush blocking module will block the relay, which may delay the removal of the slight fault and lead to more serious faults. To address this problem, this paper proposes a data-aided power transformer differential protection without inrush blocking module. The key to eliminating the negative influence of inrush current is to extract the fundamental component from the non-inrush part of the current waveform, which corresponds to the unsaturation period of the transformer core. Firstly, a data-aided module, namely an Attention module embedded Fully Convolutional Network (A-FCN), is built to distinguish the inrush and non-inrush parts of the current waveform. Then, a physical model of the current waveform is built for the non-inrush part, and the fundamental component is extracted by the nonlinear least square (NLS) algorithm. The proposed method can avoid the block of differential protections when inrush current occurs, which improves the sensitivity and rapidity of the relay, especially in the case of a weak internal fault hidden in inrush current. Finally, simulation and experimental data verify the effectiveness and generalization of the proposed method.
title A Data-Aided Power Transformer Differential Protection without Inrush Blocking Module
topic Systems and Control
url https://arxiv.org/abs/2604.01928